3m Company. According to Code for Design of Automatic Fire Alarm System (GB50116—2013), the distance between the panel and the wall of the fire control room should not be less than 3m. The operating distance in front of the equipment panel in the fire control room should not be less than 1.5m in single row arrangement and not less than 2m in double row arrangement.